Roger W. Griffith, P.E.

  • Home
  • About Roger
  • Engineering
    • Plumbing
    • Hot Water Scalding
    • Carbon Monoxide Poisoning
    • Legionella
  • Expert Witness
  • Blog
  • Contact

Duct Smoke Detectors – Locate In Supply or Return Ducts?

May 8, 2015 by Roger Griffith 11 Comments

duct smoke detector

Duct smoke detectors, when installed in HVAC systems, automatically stop the system fans upon the detection of smoke. For HVAC systems with airflows exceeding 2,000 cfm, duct smoke detectors are required. This includes where multiple air handling systems utilize common ducts with a combined design capacity greater than 2,000 cfm.

But when duct smoke detectors are required, where should they be located? Let’s look at the requirements in two of the prominent codes and standards.

Code Requirements

2012 International Mechanical Code (IMC)
The 2012 IMC requires duct smoke detectors to be located in the return air duct or plenum upstream of any filters, exhaust air connections, outdoor air connections, or decontamination equipment and appliances. Return system smoke detectors are not required where the entire space served by the air distribution system is protected by a system of area smoke detectors connected to a fire alarm system in accordance with the International Fire Code.

NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems, 2012
NFPA 90A requires duct smoke detectors to be located in the supply duct downstream of air filters and ahead of any branch connections. For air distribution systems serving more than one story and having a capacity greater than 15,000 cfm, smoke detectors are also required in the return system at each story prior to any recirculation or fresh air inlet connection. Return system smoke detectors are not required where the entire space served by the air distribution system is protected by a system of area smoke detectors. Smoke detectors are not required in exhaust ducts.

The conflicting requirements are obvious. The IMC requires smoke detectors in the return ducts. NFPA 90A requires smoke detectors in the supply ducts. Given this, how should a design engineer proceed?

How to Decide

First, determine what are the governing code(s) for your particular project. If the IMC is the adopted code, then require smoke detectors in the return ducts. That may be the only code requirement. NFPA 90A is not referenced in the IMC. But you must also check the requirements of the fire officials in the jurisdiction of the project. If they have adopted NFPA 101 or other NFPA standards that reference NFPA 90A, compliance with NFPA 90A requirements may be mandated by the fire officials. If so, locate smoke detectors in the supply and return ducts.

I understand this doesn’t make much sense from an engineering standpoint, but if the building inspector requires smoke detectors in the return ducts and the fire inspector requires the smoke detectors in the supply ducts and neither will accept other locations, there is no other way to solve the dilemma.

Hopefully, at some future time, these codes and standards can find a location for the smoke detectors they can both agree on.


For topics on future blog posts, make a suggestion.

Facebook0Tweet0LinkedIn0Print0Email0

Filed Under: HVAC, International Mechanical Code Tagged With: NFPA 90A

Comments

  1. nisanth says

    December 5, 2016 at 12:42 am

    (y?)

    Reply
  2. nisanth says

    December 5, 2016 at 12:43 am

    good explanation

    Reply
    • Roger Griffith says

      December 7, 2016 at 10:58 am

      Thank you. I hope it was helpful.

      Reply
  3. nisanth says

    December 5, 2016 at 12:55 am

    sir, so as per NFPA we can exclude smoke detector in return if the building protected with smoke detector??

    Reply
    • Roger Griffith says

      December 7, 2016 at 11:09 am

      Yes, according to NFPA 90A-2012, paragraph 6.4.2.2 states, “Return system smoke detectors shall not be required where the entire space served by the air distribution system is protected by a system of area smoke detectors.” Note that the “entire space served by the air distribution system” must be protected by a system of area smoke detectors.

      Of course, also verify that the fire marshal/plans reviewer is in agreement. In addition, remember that the building/mechanical code may require duct smoke detectors in the return system, as is noted in this blog post.

      Reply
  4. Lindsey Smith says

    April 24, 2018 at 4:04 pm

    i am thankful I found this. This was very helpful.

    Reply
    • Roger Griffith says

      April 25, 2018 at 4:36 pm

      I am glad to hear that the post was helpful to you. Hopefully, I can provide more content in the future that will be helpful.

      Reply
  5. Rotceh says

    October 16, 2018 at 12:14 pm

    Greetings,

    Why is 2,000 CFM the specific number requiring a smoke detector? Other than that is the number provided in various codes?

    Reply
    • Roger Griffith says

      October 17, 2018 at 10:34 am

      The International Mechanical Code (IMC) Code Commentary states, “Return air systems with design capacities equal to or less than 2,000 cfm are exempt from this requirement because their small size limits their capacity for spreading smoke to parts of the building not already involved with fire. The area that could be served by a 2,000 cfm system (approximately 5 tons of cooling capacity) is comparatively small. Therefore, the distribution of smoke in a system of that size would be minimal.

      Even with that explanation, the 2,000 cfm limit still appears to be somewhat arbitrary. I have always assumed the fact that 5-ton units are the transition point between residential and commercial units may be a factor in the selection of that value.

      Reply
  6. SmokieJoe says

    August 6, 2019 at 11:18 am

    This may seem like a dumb question but who’s responsibility is it to locate duct detectors the Mechanical engineer or the fire alarm engineer? I would think the mechanical engineer is responsible for where and when the detection required, the fire alarm engineer is responsible for how the detection is provided.

    Reply
    • Roger Griffith says

      August 11, 2019 at 4:24 pm

      SmokieJoe, I agree with your assessment. HVAC designers have the responsibility to determine when smoke detectors are required and the location. Both of these requirements are covered in the mechanical codes. It is good practice to locate the smoke detectors on your plans.

      Typically, the mechanical contractor installs the duct smoke detector and the electrical or fire alarm contractor wires them up, which also aligns with this practice.

      Reply

LEAVE A COMMENT: Thanks for leaving a comment. All comments are moderated. Your email address will NOT be published. Let's have a personal and meaningful conversation. Cancel reply

This site uses Akismet to reduce spam. Learn how your comment data is processed.

Contact Me

Roger W. Griffith, P.E.
(865) 471-8142
RGriffith@GriffithEngineering.net

Read More…

Get all the latest content delivered to your inbox. (No spam; I promise)

See more content from Roger

  • Facebook
  • Twitter
  • LinkedIn
  • Email

Recent Posts

  • Sleeper Sofas and Gas Appliances
  • Careful! The Wrong Showerhead May Scald You
  • Roger W. Griffith appointed to ICC Plumbing/Mechanical/Fuel Gas Code Action Committee
  • Tools and Resources for Mechanical Insulation
  • Can Sprinklers Removed From A System Be Reattached?

Categories

  • Carbon monoxide poisoning
  • Gas appliances
  • Hot Water Scalding
  • Hot Water Systems
  • HVAC
  • International Fuel Gas Code
  • International Mechanical Code
  • International Plumbing Code
  • Legionella
  • Plumbing
  • Recent Posts
  • Sprinkler Systems
  • Uncategorized
  • Water Heaters

Recent tweets

Tweets by RogerGriffith

Roger W. Griffith, P.E.
P.O. Box 702
Jefferson City, TN 37760
(865) 471-8142

Email: rgriffith@griffithengineering.net

Site Links

  • Home
  • About Roger
  • Expert Witness
  • Engineering
  • Blog
  • Privacy Policy
  • Contact

What can we help you find?

See more content

  • Facebook
  • Twitter
  • LinkedIn
  • Email

Copyright © 2021 · Agency Pro Theme on Genesis Framework · WordPress · Log in

Share this ArticleLike this article? Email it to a friend!

Email sent!