Where Should Duct Smoke Detectors Be Located?

May 8, 2015 by Roger Griffith 5 Comments

duct smoke detector

Duct smoke detectors, when installed in HVAC systems, automatically stop their respective fans upon the detection of smoke. For HVAC systems with airflows exceeding 2,000 cfm, duct smoke detectors are required. This includes where multiple air handling systems utilize common ducts with a combined design capacity greater than 2,000 cfm.

But when duct smoke detectors are required, where should they be located? Lets look at the requirements in two of the prominent codes and standards.

2012 International Mechanical Code (IMC)
The 2012 IMC requires duct smoke detectors be located in the return air duct or plenum upstream of any filters, exhaust air connections, outdoor air connections, or decontamination equipment and appliances. Return system smoke detectors are not required where the entire space served by the air distribution system is protected by a system of area smoke detectors connected to a fire alarm system in accordance with the International Fire Code.

NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems, 2012
NFPA 90A requires duct smoke detectors to be located in the supply duct downstream of air filters and ahead of any branch connections. For air distribution systems serving more than one story and having a capacity greater than 15,000 cfm, smoke detectors are also required in the return system at each story prior to any recirculation or fresh air inlet connection. Return system smoke detectors are not required where the entire space served by the air distribution system is protected by a system of area smoke detectors. Smoke detectors are not required in exhaust ducts.

The conflicting requirements are obvious. The IMC requires smoke detectors in the return ducts. NFPA 90A requires smoke detectors in the supply ducts. Given this, how should a design engineer proceed?

First, determine what are the governing code(s) for your particular project. If the IMC is the adopted code, then require smoke detectors in the return ducts. That may be the only code requirement. NFPA 90A is not referenced in the IMC. But you must also check the requirements of the fire officials in the jurisdiction of the project. If they have adopted NFPA 101 or other NFPA standards that reference NFPA 90A, compliance with NFPA 90A requirements may be mandated by the fire officials. If so, locate smoke detectors in the supply and return ducts.

I understand this doesn’t make much sense from an engineering standpoint, but if the building inspector requires smoke detectors in the return ducts and the fire inspector requires the smoke detectors in the supply ducts and neither will accept other locations, there is no other way to solve the dilemma.

Hopefully, at some future time these codes and standards can find a location for the smoke detectors they can both agree on.

Share this:

  • Share
  • Twitter
  • LinkedIn
  • Google
  • Email
  • Print

Related

Filed Under: HVAC, International Mechanical Code, NFPA 90A

Comments

  1. nisanth says

    December 5, 2016 at 12:42 am

    (y?)

    Reply
  2. nisanth says

    December 5, 2016 at 12:43 am

    good explanation

    Reply
    • Roger Griffith says

      December 7, 2016 at 10:58 am

      Thank you. I hope it was helpful.

      Reply
  3. nisanth says

    December 5, 2016 at 12:55 am

    sir, so as per NFPA we can exclude smoke detector in return if the building protected with smoke detector??

    Reply
    • Roger Griffith says

      December 7, 2016 at 11:09 am

      Yes, according to NFPA 90A-2012, paragraph 6.4.2.2 states, “Return system smoke detectors shall not be required where the entire space served by the air distribution system is protected by a system of area smoke detectors.” Note that the “entire space served by the air distribution system” must be protected by a system of area smoke detectors.

      Of course, also verify that the fire marshal/plans reviewer is in agreement. In addition, remember that the building/mechanical code may require duct smoke detectors in the return system, as is noted in this blog post.

      Reply

Leave a Reply Cancel reply

Contact Me

Roger W. Griffith, P.E.
(865) 471-8142
RGriffith@GriffithEngineering.net

Read More…

SUBSCRIBE TO MY NEWSLETTER

Get all the latest content.
(No spam; I promise)

  • Email
  • Facebook
  • Google+
  • Linkedin
  • Twitter
  • YouTube

Recent Posts

  • Roger W. Griffith appointed to ICC Plumbing/Mechanical/Fuel Gas Code Action Committee
  • Tools and Resources for Mechanical Insulation
  • Can Sprinklers Removed From A System Be Reattached?
  • How To Design Plumbing Systems To Minimize Legionella
  • Thermal Expansion Tanks: Part 3

Categories

  • Dry System
  • Hot Water Systems
  • HVAC
  • International Fuel Gas Code
  • International Mechanical Code
  • International Plumbing Code
  • Legionella
  • NFPA 13
  • NFPA 13R
  • NFPA 90A
  • Plumbing
  • Recent Posts
  • Scalding
  • Sprinkler Systems
  • Uncategorized
  • Water Heaters

Connect on Twitter?

My Tweets

Roger Griffith, P.E.
P.O. Box 702
Jefferson City, TN 37760
(865) 471-8142

  • Home
  • About Roger
  • Engineering
    • Plumbing
    • Hot Water Scalding
    • Carbon Monoxide Poisoning
    • Legionella
  • Expert Witness
  • Blog
  • Contact

Follow Me on Social Media

  • Email
  • Facebook
  • Google+
  • Linkedin
  • Twitter
  • YouTube

Copyright © 2018 · Agency Pro Theme on Genesis Framework · WordPress · Log in

loading Cancel
Post was not sent - check your email addresses!
Email check failed, please try again
Sorry, your blog cannot share posts by email.